Jumo 705020 mTRON T - Analog Input Module, 4-Ch. Operat Uživatelský manuál Strana 55

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 70
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 54
55
7 Configuration – in setup program only
7.1.1 Grid points
Customer-specific linearization is specified by entering up to 45 grid points (pairs of values X/
Y). Here, value X indicates the physical measured value (e.g. in mV, mA, or Ohm; depending
on the sensor type) and value Y indicates the linearized value (e.g. temperature in °C).
Setup dialog
Parameter
The domain of the linearization (measured values, x-axis) is checked in the module and limited
as follows:
Domain lower limit = Xmin - 0.0125 × (Xmax - Xmin)
Domain upper limit = Xmax + 0.03125 × (Xmax - Xmin)
Parameter Selection/settings Description
Measured value
(X)
-99999 to 0 to +99999 Value of the relevant grid point on the x-
axis
Linearized value
(Y)
-99999 to 0 to +99999 Value of the relevant grid point on the y-
axis
TIP!
A measured value beyond the domain limits causes an overange or an underrange (out-of-
range).
Zobrazit stránku 54
1 2 ... 50 51 52 53 54 55 56 57 58 59 60 ... 69 70

Komentáře k této Příručce

Žádné komentáře