Jumo 705021 mTRON T - Analog Input Module, 8-Ch. Operat Uživatelský manuál Strana 32

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 56
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 31
6 Configuration
32
6.2 Analog inputs
The eight analog inputs are measuring inputs for RTD temperature probes in 2-wire circuit.
Setup dialog
Parameter
Parameter Selection/settings Description
Sensor Selection of measuring probe for the relevant analog input
No choice No sensor selected
RTD temp. probe 2-w RTD temperature probe in 2-wire circuit
Linearization Available options and factory settings depend on the measuring probe selected.
Linear
Pt100 DIN EN 60751
Pt500 DIN EN 60751
Pt1000 DIN EN 60751
Pt100J JIS 1604
Pt100G GOST 6651-94
Scale
start
Factory setting depends on the linearization.
-99999 to +99999 Start value of display range
Scale
end
Factory setting depends on the linearization.
-99999 to +99999 End value of display range
TAG number 7 characters Identification marking (documentation in
PLC)
Unit 5 characters (%) Unit for numerical representation of
measured value