Jumo 705021 mTRON T - Analog Input Module, 8-Ch. Operat Uživatelský manuál Strana 37

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 56
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 36
37
6 Configuration
Performing fine adjustment
1) Determine the lower value (as low and constant as possible) with the reference measuring
device.
Example: Set furnace temperature to 20 °C.
2) Enter the display value as the actual start value and the reference value as the target start
value.
Example: Enter 15 and 20.
3) Determine the upper value (as high and constant as possible) with the reference measuring
device.
Example: Increase furnace temperature to 80 °C.
4) Enter the display value as the actual end value and the reference value as the target end
value.
Example: Enter 70 and 80.
Characteristic line
The following diagram shows the changes in the characteristic line caused by the fine adjust-
ment (point of intersection with the x axis as well as the gradient).
Resetting the fine adjustment
The following settings must be made to reverse the fine adjustment:
Actual start value = target start value
Actual end value = target end value
20 80
20
80
70
15
(2)
y
(1)
x
y Display value (1) Characteristic line before fine adjustment
x Reference value (2) Characteristic line after fine adjustment
Zobrazit stránku 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 55 56

Komentáře k této Příručce

Žádné komentáře