4 Electrical connection
26
4.3.2 Digital input
The connection depends on the configuration (input or output).
4.3.3 Digital outputs
The connection depends on the configuration (input or output).
Connection Input Terminals Symbol and terminal designation
Apply signal DC 0/24 V to ter-
minals 1to12
Ground reference via GND ter-
minal required!
1
2
3
4
5
6
7
8
9
10
11
12
1 and GND
2 and GND
3 and GND
4 and GND
5 and GND
6 and GND
7 and GND
8 and GND
9 and GND
10 and GND
11 and GND
12 and GND
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12
GND
Or:
Switch DC 24 V from terminal
+24V to terminals 1to12 via
floating contact.
External voltage supply
DC 24 V via terminals +24 V
and GND required!
1
2
3
4
5
6
7
8
9
10
11
12
1and+24V
2and+24V
3and+24V
4and+24V
5and+24V
6and+24V
7and+24V
8and+24V
9and+24V
10 and +24 V
11 and +24 V
12 and +24 V
+24 V
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12
Connection Output Terminals Symbol and terminal designation
Output signal:
DC 0/24 V / maximum 500 mA
External voltage supply
DC 24 V via terminals +24 V
and GND required!
1
2
3
4
5
6
7
8
9
10
11
12
1andGND
2andGND
3andGND
4andGND
5andGND
6andGND
7andGND
8andGND
9andGND
10 and GND
11 and GND
12 and GND
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12
GND